Are you a homeowner or building manager?
Find a Contractor »

Tech Challenge – November 2018


Posted on:

A frozen food case utilizing R-507A with a TXV metering device (and receiver) has a customer complaint of “warm product.” The symptoms at the convenience store confirm that the case is 20 degrees warmer than normal and the condensing unit appears to be cycling on the low pressure control. What are the “possible causes” (note: there is only one problem intended) with the following measured conditions on this field service check sheet?

Field Service Check Sheet

Compressor Discharge Temp. 92 deg. F
Condensing Press./Temp. 203 psig / 88 deg. F.
Condensing Outlet 81 deg. F.
Condenser Sub cooling 7 deg. F.
Condenser Split 13 deg. F.
Entering Feed Device Temp. 77 deg. F.
Evaporator Press./Temp. 29 psig / -6 deg. F.
Evaporator Outlet Temp. -3 deg. F.
Evaporator Superheat 3 deg. F.
Compressor Inlet Temp. 2 deg. F.
Total S. H. 8 deg. F.
Ambient Temp. 75 deg. F.
Room/Box Temp.34 20 deg. F
Compressor Volts 240 V.
Compressor Amp. Draw Normal

Looking for the Answer: Check hvac-blog.acca.org on December 31, 2018, for the answer to this issue’s Tech Challenge.


Posted In: ACCA Now, Tech Challenge

Looking for an ACCA QA Accredited Contractor?

Are you a homeowner or building manager?

BECOME AN ACCA MEMBER

join now

PLUS It's Risk Free!