A commercial rooftop utilizing R-410A with a TXV feed device(and receiver)has a manager complaint of “no cooling.”The symptoms confirm inadequate cooling and the condensing unit and blower appears to be running all of the time and the thermostat is not satisfied. What are the “possible causes” (Note: There is only one problem intended) with the following measured conditions on this field service check sheet?

Field Service Check Sheet

Compressor Discharge Temp. 228 deg. F
Condensing Press./Temp. 390 psig / 115 deg. F.
Condensing Outlet 98 deg. F.
Condenser Sub cooling 17 deg. F.
Condenser Split 27 deg. F.
Entering Feed Device Temp. 8 deg. F.
Evaporator Press./Temp. 130 psig / 45 deg. F.
Evaporator Outlet Temp. 56 deg. F.
Evaporator Superheat 11 deg. F.
Compressor Inlet Temp. 68 deg. F.
Total S. H. 23 deg. F.
Ambient Temp. 88 deg. F.
Room/Box Temp. 78 deg. F
Compressor Volts 240 V.
Compressor Amp. Draw High

Looking for the answer? Check back June 30, 2019.