Are you a homeowner or building manager?
Find a Contractor »

Tech Challenge January 2023


Posted on:

A logo of a yellow, red, blue, and green rubix cube with one square out of place and "Tech Challenge" written beneath it

A reach-in cooler utilizing R-134a with a capillary tube feed device has a customer complaint of warm beer. The symptoms at the convenience store confirm inadequate cooling and the compressor appears to be short cycling on the high or low pressure control. What are the “possible causes” (Note: There is only one problem intended) with the following measured/calculated conditions on this field service check sheet?

Field Service Check Sheet

Compressor Discharge Temp.  205 deg. F
Condensing Press./Temp. 108 psig / 92 deg. F.
Condensing Outlet  76 deg. F.
Condenser Sub cooling  16 deg. F.
Condenser Split  17 deg. F.
Entering Feed Device Temp.  44 deg. F.
Evaporator Press./Temp.  5 psig / -3 deg. F.
Evaporator Outlet Temp.  37 deg. F.
Evaporator Superheat  40 deg. F.
Compressor Inlet Temp.  68 deg. F.
Total S. H.  71 deg. F.
Ambient Temp.  75 deg. F.
Room/Box Temp.  51 deg. F
Compressor Volts  240 V.
Compressor Amp. Draw  Low

Come back in February to get the answer.


Posted In: ACCA Now, Tech Challenge

Looking for an ACCA QA Accredited Contractor?

Are you a homeowner or building manager?

BECOME AN ACCA MEMBER

join now

PLUS It's Risk Free!