A rooftop utilizing R-410A with a TXV feed device has a customer complaint of insufficient cooling.The symptoms confirm inadequate cooling and the compressor appears to be short cycling. What are the “possible causes” (Note: There is only one problem intended) with the following measured/calculated conditions on this field service check sheet?
Field Service Check Sheet
Compressor Discharge Temp.                                                               249 deg. F.
Condensing Press./Temp.                                                                      444 psig / 125deg. F.
Condensing Outlet Temp.                                                                         90 deg. F.
Condenser Sub cooling                                                                              35 deg. F.
Condenser Split                                                                                           37 deg. F.
Entering Feed Device Temp.                                                                    90 deg. F.
Evaporator Press./Temp.                                                                        157 psig / 55deg. F.
Evaporator Outlet Temp.                                                                         68 deg. F.
Evaporator Superheat                                                                                13 deg. F.
Compressor Inlet Temp.                                                                           73 deg.F.
Total S. H.                                                                                                    18 Deg. F.
Ambient Temp.                                                                                           88 deg. F.
Room/Box Temp.                                                                                      78  deg. F.
Compressor Volts                                                                                    240 V.
Compressor Amp. Draw                                                                        High