A rooftop system utilizing R-22 with a fixed orifice metering device has a manager’s complaint of “no cooling.” The symptoms at the store confirm that the thermostat is not satisfied and the condensing unit and blower are running continuously. What are the “possible causes” (there is only one problem intended) with the following measured conditions on this field service check sheet?
Field Service Check Sheet
Compressor Discharge Temp. | 230 deg. F. |
Condensing Press./Temp. | 390 psig / 115 deg. F. |
Condensing Outlet Temp. | 88 deg. F. |
Condenser Sub cooling | 27 deg. F. |
Condenser Split | 35 deg. F. |
Entering Feed Device Temp. | 82 deg. F. |
Evaporator Press./Temp. | 129 psig / 45 deg. F. |
Evaporator Outlet Temp. | 50 deg. F. |
Evaporator Superheat | 5 deg. F. |
Compressor Inlet Temp. | 66 deg. F. |
Total S. H. | 25 Deg. F. |
Ambient Temp. | 80 deg. F. |
Room/Box Temp. | 84 deg. F |
Compressor Volts | 240 V. |
Compressor Amp. Draw | High |