May/June 2024 Tech Challenge Answer
Posted on:
A medium temperature beverage cooler utilizing R-134a with a TXV metering device and liquid receiver has a customer complaint of warm beer. The symptoms at the convenience store confirm inadequate cooling and the compressor appears to be short cycling on the high- or low-pressure control. What are the “possible causes” (note: there is only one problem intended) with the following measured/calculated conditions on this field service check sheet?
Field Service Check Sheet
- Compressor Discharge Temp. 231 deg. F.
- Condensing Press./Temp. 255 psig / 148 deg. F.
- Condensing Outlet Temp. 98 deg. F.
- Condenser Sub cooling 50 deg. F.
- Condenser Split 73 deg. F.
- Entering Feed Device Temp. 85 deg. F.
- Evaporator Press./Temp. 22 psig / 25 deg. F.
- Evaporator Outlet Temp. 40 deg. F.
- Evaporator Superheat 15 deg. F.
- Compressor Inlet Temp. 68 deg. F.
- Total S. H. 43 Deg. F.
- Ambient Temp. 75 deg. F.
- Room/Box Temp. 50 deg. F.
- Compressor Volts 240 V.
- Compressor Amp. Draw Normal/High
Answer: The possible cause of the warm beverages appears to be a dirty, restricted air flow, recirculated air, condenser fan, or fan blade issue. The condensing pres/temp. is high to reject the heat picked up in the evaporator, S.H.(evaporator and suction line), and compressor. The high compression ratio of 7.3 (absolute discharge pressure of 269.7PSIA, divided by the absolute suction pressure of 36.7PSIA) is causing recompression and a very high discharge temperature. The subcooling and superheat are high to near normal because the TXV is attempting to maintain a constant S.H. with a lower refrigerant flow rate caused by the higher compression ratio.
Click here to read the latest edition of ACCA Now Magazine.
- May/June 2024 Tech Challenge Answer - June 14, 2024
- March/April 2024 Tech Challenge Answer - April 25, 2024
- January/February 2024 Tech Challenge Answer - February 23, 2024
Posted In: ACCA Now, Tech Challenge