March 2019 Tech Challenge
Posted on:
A rooftop system utilizing R-22 with a fixed orifice has a customer complaint of insufficient cooling.The symptoms confirm the thermostat is not satisfied and the blower and compressor appear to be running all of the time. What are the “possible causes” (Note: There is only one problem intended) with the following measured conditions on this field service check sheet?
Field Service Check Sheet
| Compressor Discharge Temp. | 241 deg. F |
| Condensing Press./Temp. | 262 psig / 121 deg. F. |
| Condensing Outlet | 98 deg. F. |
| Condenser Sub cooling | 23 deg. F. |
| Condenser Split | 41 deg. F. |
| Entering Feed Device Temp. | 88 deg. F. |
| Evaporator Press./Temp. | 90 psig / 54 deg. F. |
| Evaporator Outlet Temp. | 62 deg. F. |
| Evaporator Superheat | 8 deg. F. |
| Compressor Inlet Temp. | 65 deg. F. |
| Total S. H. | 11 deg. F. |
| Ambient Temp. | 80 deg. F. |
| Room/Box Temp. | 82 deg. F |
| Compressor Volts | 240 V. |
| Compressor Amp. Draw | High |
Looking for the answer? Check back on April 30, 2019.