An Easy Retrofit for Return Air
Posted on:
A bedroom really doesn’t aspire to be a balloon. Yet, because of the way the heating and air conditioning system was installed, it may be acting like one. At least to an extent. It doesn’t expand the way a balloon does, but it does get blown up. If the bedroom has a supply vent from your HVAC system but no return vent or other pathway for the air to make its way back to the unit, what happens to that air blowing into the room when the occupant closes the door?
The problem with bedrooms
Forced-air heating and cooling systems use ducts to move conditioned air from the furnace, heat pump, or air conditioner into the living space inside the house. The air that it’s conditioning, though, isn’t just whatever it can get. Ideally, it’s a closed system with as little duct leakage as possible, and the air that it’s conditioning comes from inside the house. The furnace or air handler pulls air through the return ducts, conditions that air, and then sends it through the supply ducts back into the house.
The problem with bedrooms occurs in houses where the HVAC design did not include return vents in each bedroom. Well, I should say it’s only a potential problem because a good installer will be working from an actual HVAC design, which should specify exactly how air gets back to the air handler. If a home has a central return vent for all the air going to the air handler, a good HVAC design will include return air pathways from the bedrooms. That could be jumper ducts or transfer grilles. Door undercuts typically won’t allow enough air to get out of the bedroom unless you leave a gap bigger than most people want under their doors (more on that in a future article).
The consequences of inadequate return air pathways
What happens if you don’t make provisions for the return air from the bedrooms? When the system is running and the bedroom door is closed, the pressure in the bedroom goes up. It becomes positive relative to the main part of the house and probably also to the outdoors. Some of that air will find its way under the door and through interior leaks back to the central return vent. The rest of it, though, will push through openings and leak to the outdoors and into interstitial spaces. It leaks out. The homeowner loses air they’ve paid to heat or cool.
The other side of that pressure equation is what happens in the main part of the house. If the bedroom doors are closed and the bedrooms become positively pressurized, the main part of the house sees negative pressure. The central return is pulling air, but can’t get everything back from the bedrooms. That negative pressure can be a big problem.
Negative pressure in the house can cause a number of problems:
- Infiltration – Since the central return can’t pull back all the air the AHU sent to the bedrooms, it pulls it from wherever it can, including unconditioned air from outside.
- Bad air from outside – Some of that air pulled in from outside may be nasty air full of fumes from the garage or moldy air from the crawl space.
- Backdrafting – If that negative pressure extends to the location of a natural draft gas water heater, you may end up with air coming down the flue instead of exhaust gases going up the flue. This backdrafting can result in carbon monoxide coming into the living space. What’s worse, that central return pulls the carbon monoxide into the air handler and distributes it to the bedrooms.
Return air pathways are important.
An easy retrofit
If you called to a house that doesn’t have dedicated return vents in the bedrooms and there’s also no hint of jumper ducts or transfer grilles, you have another option. Tamarack Technologies makes something they call the Perfect Balance in-door return air pathway. (Disclosure: Tamarack is an advertiser here in the Energy Vanguard Blog. We like their stuff and think you will, too.) They’re inexpensive, easy to install, and they work. Here’s a video showing the pressure difference with and without the Perfect Balance.
I installed these return air pathways in my condo three years ago, and that video shows the one in our guest bedroom, where the positive pressure created by the lack of a return air pathway was the worst. It made a huge difference, dropping the pressure in the bedroom (relative to the hallway) from about 6.7 Pascals (Pa) to about 1.7 Pa. The ENERGY STAR new homes program requires pressure balancing of bedrooms with a maximum pressure difference of 3.0 Pa.
It took me about a half hour to install these things in all three bedroom doors. All I had to do was remove the door from the hinges, place it on sawhorses, trace the outline of the piece using the template provided, cut out the section of the door, screw the piece to the bottom of the door, and then put the door back on the hinges. Bam!
If you’re worried about privacy, the Perfect Balance has a cardboard baffle built in to reduce sound transmission. I’ve lived with them in my condo for three years now and have never had a problem. By getting down on the floor and putting your face up against it, you can see through into the bedroom, but you get a limited, narrow view of the other side.
The best use of the Perfect Balance is in existing homes where you don’t have returns in the bedrooms and can’t (or don’t want to) install jumper ducts or transfer grilles. If the pressure in the bedroom with the door closed and the air handler running is higher than 3 Pa, this is a great way to retrofit a return air pathway. If you don’t like the look of the Perfect Balance, Tamarack also sells transfer grilles, which you install in a wall.
When you’re in a home with a central return, think about that pressure building up in the bedrooms. Imagine where that air might be going. Imagine the kind of air that’s coming in from outside.
It’s time to pop that balloon.