September 2023 Tech Challenge
Posted on:
Share this challenge with your staff and see who can figure out the diagnosis first.
A frozen food case utilizing R-404A with a TXV metering device (and receiver) has a customer complaint of “warm case.” The symptoms at the store confirm that the case is 20 degrees warmer than normal, and the condensing unit is running continuously. What are the “possible causes” (note: there is only one problem intended) with the following measured conditions on this field service check sheet?
Note: There is only one problem intended.
Field Service Check Sheet
- Compressor Discharge Temp. 225 deg. F.
- Condensing Press./Temp. 187 psig / 84 deg. F.
- Condensing Outlet Temp. 81 deg. F.
- Condenser Subcooling 3 deg. F.
- Condenser Split 14 deg. F.
- Entering Feed Device Temp. 78 deg. F.
- Evaporator Press./Temp. 15 psig / -22 deg. F.
- Evaporator Outlet Temp. 12 deg. F.
- Evaporator Superheat 32 deg. F.
- Compressor Inlet Temp. 48 deg. F.
- Total S. H. 54 deg. F.
- Ambient Temp. 70 deg. F.
- Room/Box Temp. 20 deg. F.
Check back during the first week of October for the answer!
- May/June 2024 Tech Challenge Answer - June 14, 2024
- March/April 2024 Tech Challenge Answer - April 25, 2024
- January/February 2024 Tech Challenge Answer - February 23, 2024
Posted In: ACCA Now, Tech Challenge