Are you a homeowner or building manager?
Find a Contractor »

Impact of Installation Faults on Heat Pump Performance


Posted on:

Numerous studies and surveys indicate that typically-installed HVAC equipment operate inefficiently and waste considerable energy due to varied installation errors (faults) such as improper refrigerant charge, incorrect airflow, oversized equipment, and leaky ducts. This article summarizes the results of a large United States (U.S.) experimental/analytical study (U.S. contribution to IEA HPP Annex 36) of  the impact that different faults have on the performance of an air-source, single-speed heat pump (ASHP) in a typical U.S. single-family house. It combines building effects, equipment effects, and climate effects in an evaluation of the faults’ impact on seasonal energy consumption through simulations of the house/ASHP pump system.

Introduction

Click to enlarge
Click to enlarge

The U.S. technical contribution to Annex 36 (Domanski et al., 2014) explores the impact that typical installation faults have on the performance of a single-speed, 8.8 kW (2.5-ton), ducted, split-system ASHP installed in a single-family house; rated seasonal cooling and heating performance factors (SPFc and SPFh) of 3.81 W/W and 2.26 W/W (U.S. SEER and HSPF of 13 Btu/Wh and 7.7 Btu/ Wh), respectively. The laboratory/ modeling project combined building, equipment, and climate effects in a comprehensive evaluation of the impact of installation faults on annual energy consumption of the ASHP via seasonal simulations of the house/ heat pump system. Faults were evaluated both individually and in combination. The fault parameters evaluated in the study are listed in Table 1. The fault parameters were based on
the requirements found in the ANSI/ ACCA 5 QI – 2010 Standard “HVAC Quality Installation Specification” (ACCA, 2010), along with two additional faults: excessive liquid line refrigerant subcooling and undersized field-installed thermal expansion valve (TXV). The annual energy consumption analyses were conducted for two different house types (one with a slab foundation and a second with basement foundation) in five locations representative of the range of U.S. climate condition.

Laboratory Analysis

Click to enlarge
Click to enlarge

The undertaken laboratory analyses resulted in correlations that characterize the ASHP performance with no faults (baseline case) and with the first seven faults listed in Table 1. The last two faults in Table 1 were modeled only. Figures 1 and 2 illustrate the indoor and outdoor sections, respectively, of the ASHP as installed in the environmental test chambers at the U.S. National Institute of Standards and Technology (NIST). Figure 3 illustrates the measured impact of indoor air flow faults on the test heat pump COP. Full details and results of the lab tests may be found in Domanski et al. (2014).

Simulations of Building/ASHP Systems with Installation Faults

Click to enlarge
Click to enlarge

These simulations, using the laboratory-determined performance correlations, estimated the annual energy consumption (combined heating and cooling) of the subject ASHP for both normal (baseline or no fault) operation and for various intensities of the studied installation faults. The simulations focused strictly on system performance issues; no effort was made to quantify impacts on occupant comfort, indoor air quality, noise generation (e.g., airflow noise from air moving through restricted ducts), equipment reliability/robustness (number of starts/stops, etc.), maintainability (e.g., access issues), or costs of initial installation and ongoing maintenance.

A building model developed in TRNSYS was used to simulate the integrated performance of the subject ASHP/house systems in this study (CDH Energy Corp., 2010). The model is driven by typical meteorological year weather data sets TMY3 (Wilcox and Marion, 2008) on a small time-step (e.g., 1.2 minutes).

Table2GlennArticle
Click to enlarge

A detailed thermostat model turns the heat pump “on” and “off” at the end of each time step, depending on the calculated space conditions.
Table 2 lists the climates with representative locations and house structures considered in this study. The selected cities represent U.S. climate zones 2 through 6 as shown in Figure 4. This selection enabled prediction of how different faults will affect ASHP performance in the most prevalent climates in the U.S.

Click to enlarge
Click to enlarge

Two 190 m2 (2,000 ft2) three-bedroom houses were modeled: a slab-ongrade house, and a house with a basement. A 2-zone model was employed for the slab-on-grade foundation house – living space and attic zones. A 3-zone model was developed for the basement foundation house – living space, attic, and basement zones. The basement was not directly conditioned, but coupled to the main living space via zone-to-zone air exchange. These buildings corresponded to code-compliant houses with appropriate levels of insulation and other features corresponding to each climate (Domanski et al., 2014). The slab-on-grade houses were modeled with air distribution ducts located in the attic. The houses with basements were modeled with ducts located in the semi-conditioned basement space. For Houston, TX, only a slabon-grade house was studied because houses with basements are rarely built in this location.

Click to enlarge
Click to enlarge

Impact of Single Installation Faults on Heat Pump Performance
Table 3 shows representative impacts of the studied faults on ASHP annual energy use (relative to “no fault” energy use). It is anticipated that the selected levels of individual faults reflect an installation condition which might not be noticed by a poorly trained
or inattentive technician.

In most cases, the effect of installation faults is similar for both house types. Duct leakage faults (DUCT) in the slab-on-grade house can cause the highest increase in energy use among the faults studied, especially in the colder locations. It is expected that duct leakage will also result in some increase of energy use for the basement house; however, the modeling approach employed could not discern this increase.

Click to enlarge
Click to enlarge

The next most influential faults were refrigerant undercharge (UC), refrigerant overcharge (OC), and improper airflow across the indoor coil (AF). For the 30 % undercharge fault (UC) level, the energy use increase is on the order of 20 %, regardless of the climate and building type. Refrigerant overcharge (OC) can also result in a significant increase in energy use, 10 – 16 % at the 30 % overcharge fault level. Improper indoor airflow (AF) can affect similar performance degradation. [Note: Excessive refrigerant subcooling (SC) correlates to refrigerant overcharge (OC); 100 % subcooling is approximately equivalent to 20 % refrigerant overcharge.] An oversized heat pump (SIZ) coupled with undersized air ducts can cause >10 % energy use increases in the hot climate locations. The undersized cooling TXV fault (TXV) also has the potential to significantly increase the energy use in the hot locations.

Click to enlarge
Click to enlarge

Impact of Dual Installation Faults on Heat Pump Performance
The combination of two faults, A and B, were considered in the following four combinations as listed in Table 4.

The ‘moderate level’ is the value at the middle of the range, while the ‘worst level’ is the highest (or lowest) probable level of the fault value (see Table 1). In the full study (Domanski et al., 2014), simulations of 14 fault combinations were conducted: duct leakage coupled with system oversizing, restricted air flow, refrigerant overcharge or undercharge, or noncondensible gases; system oversizing
coupled with refrigerant undercharge or overcharge, or noncondensible gases; restricted air flow coupled with refrigerant undercharge or overcharge, or noncondensible gases; and undersized TXV coupled with duct leakage, system oversizing, or restricted airflow. The results indicated that the impact of combinations of two faults on annual energy use may be additive (A+B), less than additive (<A+B), or greater than additive (>A+B). Figure 5 illustrates simulation results for the combination of duct leakage and refrigerant undercharge for Houston, Washington, and Minneapolis (spanning the range of U.S. climate conditions from hot to very cold). For the lower refrigerant undercharge fault, the combined impact is approximately additive in all locations. At the greater undercharge fault level, the combined
impact is slightly amplified.

Extensive simulations of house/heat pump systems in five U.S. climatic zones lead to the following conclusions:

  • Duct leakage, refrigerant undercharge, oversized heat pump with undersized ductwork, low indoor airflow due to undersized ductwork, and
    refrigerant overcharge have the most potential for causing significant performance degradation and increased annual energy consumption.
  • The effect of different installation faults on annual energy use is similar for a slab-ongrade house and a basement house, except for the duct leakage fault.
  • The effect of two simultaneous faults can be additive (e.g., duct leakage and non-condensable gases), little changed relative to the single fault condition (e.g., low indoor airflow and refrigerant undercharge), or beyond additive (e.g., duct leakage and refrigerant undercharge).
  • The laboratory and modeling results from this fault analysis on an 8.8 kW (2.5 ton) heat pump are considered to be representative of all unitary equipment, including commercial split-systems and single package units.

ACCA, 2010. ANSI/ACCA Standard 5 QI-2010, HVAC Quality Installation Specification. Air Conditioning Contractors of America, Arlington, VA., http://www.acca.org/quality

CDH Energy Corp., 2010. TRN-RESDH5: TRNSYS Residential Dehumidifier Model – SHORT TIMESTEP. A Tool for Evaluating Hybrid Configurations and Control Options in Single-Zone Building Applications, Operating and Reference Manual. Cazenovia, NY.

Domanski, P. A., W. V. Payne, and H. I. Henderson, Jr., 2014. Sensitivity Analysis of Installation Faults on Heat Pump Performance. NIST Technical Note 1848. National Institute of Standards and Technology, Gaithersburg, MD. http://www.nist.gov/

Wilcox, S., Marion, W., 2008. User’s Manual for TMY3 Data Sets, Technical Report NREL/TP-581- 43156. National Renewable Energy Laboratory, Boulder, CO. http://www.nrel.gov/docs/fy08osti/43156.pdf

Reprinted from: Impact of Installation Faults on Heat Pump Performance, IEA Heat Pump Centre Newsletter, Volume 33 – No. 1, 2014, Glenn Hourahan & Van Baxter, pp. 34 – 38

Glenn Hourahan

Posted In: Building Performance, Residential Buildings, Technical Tips

Looking for an ACCA QA Accredited Contractor?

Are you a homeowner or building manager?

BECOME AN ACCA MEMBER

join now

PLUS It's Risk Free!